Lenexa, KS

Hyatt Place

Scope/Solutions

The six-story hotel also houses a one-story conference center at the south end. Shortly after construction, hotel personnel observed leaks at several locations. The original contractor asked SGH to investigate the leaks, develop a repair plan, and oversee repairs.

SGH investigated the reported leakage and collaborated with the contractor to develop a repair plan that could be implemented while the building remained occupied. Highlights of our repair design include the following:

  • Installing flashing and interior louver waterproofing without removing the existing windows or louvers
  • Installing pan flashing below the curtain wall by lowering the front edge of the sill to create the necessary slope for drainage
  • Developing details to integrate the weather barrier between adjacent walls systems
  • Adding through-wall flashing at the roof line and where a low roof meets a rising wall

We performed confirmation testing to verify repairs successfully addressed the issues.

Project Summary

Icon: completion-date

2019

Completion Date
Icon: construction-value

300K

Construction Value
Solutions
Repair & Rehabilitation
Services
Building Enclosures
Markets
Commercial
Client(s)
The Weitz Company, LLC
Specialized Capabilities
Condition Assessments | Roofing & Waterproofing

Key team members

Peter Babaian
Peter Babaian
Managing Principal, Building Technology, Chicago
Emily O'Keefe
Project Director

Additional Projects

Midwest

U.S. Cellular Headquarters

U.S. Cellular wanted to consolidate all Chicago-area operations, including their headquarters, into a single building where they already occupied eleven floors. SGH was the structural engineer for the renovation project, which added 120,000 sq ft to their existing space.
Explore
Midwest

Hess Corporation Tioga Office Complex

Constructed in 2009, the Tioga Office Complex is the administrative hub for Hess Corporation’s Bakken Oil Field operations. After occupying the complex, Hess personnel observed water leakage in the office building. SGH investigated the cause of leakage and recommended options for repairs.
Explore